# Truss Self-Weight & Dead Load

**Purpose**

Truss self-weight is checked against all applied dead loads to verify that there is enough assumed "extra" dead load to account for the dead load of the truss itself. Beginning with the 2024.3 release, when you apply a distributed dead load to account for self-weight, as long as the word "self" is included in the description, 100% of the dead load will be applied to, or used to account for, self-weight.

**Steps**

![](/images/csdirector-cstruss/resources/images/video-icon-33x34.png) Watch video - Part 1

![](/images/csdirector-cstruss/resources/images/video-icon-33x34.png) Watch video - Part 2

![](/images/csdirector-cstruss/resources/images/video-icon-33x34.png) 4-18-2024 Webinar featuring Truss Self Weight

![](/images/csdirector-cstruss/resources/images/video-icon-33x34.png) Mark Dead Loads as Self-Weight Loads

1. Open a truss and analyze.


If the dead load for the truss is not adequate, a message displays. The message may be either an **error message Error messages display in the following format: Dead Load does not include enough to cover self-weight of truss! Dead Load = ####, Weight = ####, Deficit = #### (##%) #### indicates the actual values used You must resolve the error message before continuing with truss design.** or a **warning message Warnings regarding the truss self weight are informational only. You can decide whether it is necessary to adjust the dead load for the truss.**.

In the example below, the error message for the truss shown indicates that the total dead load on the truss is 672 lbs. Because of the heavier lumber used and the gable truss design, the weight of the truss itself is almost 650 pounds. This leaves approximately 22 pounds of dead load to carry anything above the truss weight, which is not adequate.

![](/images/csdirector-cstruss/resources/images/ts-selfweighttrusserror-1088x571.png)

1. To resolve the error, you must calculate what is required for the truss dead load and how much is extra and can be used to counteract the self-weight of the truss.


In the following example, the applied dead load is 672, as indicated.

![](/images/csdirector-cstruss/resources/images/ts-selfweightdeadloadapplied-1194x485.png)

1. When designing trusses for Wind Loads, you must run a factored dead load case (typically 60% of the dead loads used in combination with wind loads); this ensures that the weight of materials are not overstated to reduce uplifts.


- In the example below, the factored dead load (402#) is subtracted from the dead load (672) = 270. This amount represents the "extra" amount, above the truss weight. Subtract the extra amount from the weight of the truss (650#). The result is the deficit indicated in the error message. In the example below, the deficit for this truss is 380#.


![](/images/csdirector-cstruss/resources/images/ts-selfweightdeadloadappliedfactored-1202x536.png)

**Solutions for resolving the self-weight error**

- You can adjust the deficit threshold in Env Data > Anaysis > Overall Controls > Report Self-Weight deficit larger than % as Error. This value can be set from 0% to 50% (default is 10%). This could be expressed as a decimal instead of a percent, with values Min = 0.00, Max = 0.50, Default = 0.10. If the **deficit** divided by the **weight** (times 100, if using %) is more than this setting allows, the truss fails and an error displays. Adjusting this setting may result in a warning as opposed to an error that prevents the truss from passing analysis.
- Adjust standard loads on the truss. Go to Load Template Manager > Standard Load and adjust dead loads for the truss.  ![](/images/csdirector-cstruss/resources/images/ts-selfweight-increaseload-965x518.png)
- If you know the actual weight of the materials, you can override the dead loads. Go to Load Template Manager > Wind Loads and enter the actual material weights. Be aware that if you enter amounts that total more than 60% of the dead load, you will actually be reducing the amount of available dead load for the weight of the truss.  ![](/images/csdirector-cstruss/resources/images/ts-selfweight-adjustwindload-957x470.png)
- Add additional load to the truss. Remember that when you add load, Truss Studio uses only 40% of that load as part of the truss self-weight. Go to Component > Component Loading > Distributed Load and adjust the Dead Load values. Adding a Description of **Self Weight** may be helpful to anyone reviewing the truss design. When you apply a distributed dead load to account for self-weight, as long as you include the word **self** in the Description, 100% of the dead load will be applied to, or used to account for, self-weight.   Note that when you apply a distributed dead load to account for self-weight, as long as you include the word **self** in the Description, 100% of the deal load is applied to, or used to account for, self-weight. Go to Component > Component Loading > Distributed Load to adjust Dead Load values.        ![](/images/csdirector-cstruss/resources/images/ts-selfweight-increasedeadload-963x447.png)  If this added weight is the only additional load on a single-ply or two-ply truss, check the **User Load is applied over 3 or more trusses** checkbox to maintain repetitive lumber values. If there are other loads that disqualify the use of repetitive lumber values, do not check this box. **Note:** Verify that the repetitive member factor is used properly. See Repetitive Members.  ![](/images/csdirector-cstruss/resources/images/ts-selfweight-repetitivemembercheckbox.png)
  - The load must be added as a distributed load, or loads. It can be on the TC, BC, or both. It does not need to cover the entire span, although that is typical. Note that it cannot be a point load or set of point loads, even if the other rules below are followed.
  - The added load must **only** contain dead load; if there are any other load parts, the dead load portion will not be used 100% to offset the self-weight check.
  - The description must contain the word "self" - it may be entered as "SELF", or "self" or "Self-Weight" or "Truss Self Weight" or any language desired for display on output, but must contain the word "self" in some form in the text of the description.
  - It is not necessary to add the entire amount of self-weight of the truss based on the truss weight, but only to add enough to cover the deficit noted in the error. As long as enough load is added to reduce the error to a warning, or eliminate it altogether, that is acceptable for the design.
  - If this is a common o.c. spaced truss and not a girder, remember to enable the "User load is applied over 3 or more trusses" option so that repetitive member increases are still used.


![](/images/csdirector-cstruss/resources/images/note-onlinehelp.png) **Note:** If a warning displays regarding the truss self weight, this is informational only. You can decide whether it is necessary to adjust the dead load for the truss.