# Using the MWFRS Wind Design Method

**Description**

When using the Main Wind Force Resisting System (MWFRS) design method trusses must have purlins on all top chords if the tributary area is less than 700 sq. ft.

**Design Practices**

When trusses are designed with the MWFRS design method, Components & Cladding (C&C) wind loads are not applied to the truss. The MWFRS method is only appropriate for:

- Trusses where purlins are applied to the top chord, or
- Trusses with 700 sq. ft. or greater tributary wind area


**Required Actions**

1. Determine if purlins are to be applied to the top chord based on the Construction Documents. If so, then truss(es) may be designed using the MWFRS method.


![](/images/csdirector-cstruss/resources/images/cr-trussmwfrs.jpg)

1. If the truss supports a tributary area of 700 sq. ft. or greater, the truss may be designed using the MWFRS method, regardless of whether purlins are used or not.
2. If neither of the above options are applicable, select the appropriate Design Method from the drop down list instead of MWFRS.


![](/images/csdirector-cstruss/resources/images/cr-windloaddialog-callout.png)

![](/images/csdirector-cstruss/transparent.gif)![](/images/csdirector-cstruss/resources/images/note-onlinehelp.png) **Note:** A warning note displays on-screen when MWFRS is used and purlins are not applied.

- MWFRS must be selected as the Wind Design Method; and
- Sheathing must be selected as the bracing method for any part of the top chord.  ![](/images/csdirector-cstruss/resources/images/ts-trussnotccwindloads-978x593.png)


**Related Topics**

SBC Wind Load Analysis: MWFRS vs. C&C

SBC Main Wind Force Resisting Systems Vs Components Cladding