# Application of Roof Live Load Reductions

**Description**

Roof structures, per International Building Code (IBC) Table 1607.1, must be designed for a minimum uniform roof live load of 20 PSF. This load is typically produced during maintenance by workers, equipment, and materials, or by use of the roof as a roof garden, assembly area, or for other small fixtures on the roof.

In IBC and IRC (International Residential Building Code), provisions are made which allow for reductions in roof live loads to below 20 PSF, based on the roof slope and loaded tributary area. Allowances for reduction to roof live load in the IBC are specified in sections 1607.11 and 1607.13.2. Allowances for reduction to roof live load in the IRC are specified in section R301, Table R301.6. These allowable reductions by code are built into Truss Studio, allowing you to take advantage of reductions.

The minimum allowable live load after taking reductions, by code, is 12 PSF.

**Design Practices**

In Truss Studio, the reduction factors for roof live load are calculated and applied automatically when the top chord live load (TCLL) is entered as a value less than 20 PSF. For IRC, area and pitch reductions are applied together. For IBC, the pitch reduction is applied separately from the area reduction, which can be toggled on and off.

**Required Actions**

**Designing for International Residential Building Code (IRC)**

1. When designing for roof live load reductions in IRC, navigate to Load Template Manager and open the **Std Load** dialog.
2. Set the **TC Live Load** to 10 PSF and click **OK**.


![](/images/csdirector-cstruss/resources/images/cr-roofliveloadreductionsirc.png)

Truss Studio modifies the TCLL based on allowable reductions and displays the reduced TCLL in the load template section on the main workspace.

![](/images/csdirector-cstruss/resources/images/cr-roofloadmainworkspace.png)

![](/images/csdirector-cstruss/resources/images/note-onlinehelp.png) **Note:** Although 10 PSF was entered in this example, the factored minimum TCLL is 16 PSF, based on the design parameters.

In the Code/Design information section of the TDD, the TCLL will display as 20 PSF with an asterisk and is noted for the reduction in the Loads Summary section.

![](/images/csdirector-cstruss/resources/images/cr-liveloadsreductiontcll.png)

Designing for International Building Code (IBC)

In IBC codes, the area reduction can be applied separately. In Load Template Manager, a Building Loads checkbox displays **Use Area Reduction** when IBC is selected as the building code.

![](/images/csdirector-cstruss/resources/images/cr-roofliveloadreductionsibc.png)

![](/images/csdirector-cstruss/resources/images/note-onlinehelp.png) **Note:** If you plan to apply area reduction, it should be enabled or disabled when the Standard Load is modified at the same time; otherwise, the setting will not be used. When the template changes, you are prompted to save changes and keep the selection for area reduction.

![](/images/csdirector-cstruss/resources/images/cr-areareductionspromptsave.png)

1. Turn **Use Area Reduction** on or off.
2. Modify the Standard Load TCLL to 10 PSF and click **OK**.


Truss Studio modifies the TCLL based on allowable reductions and displays the reduced TCLL in the load template section on the main workspace.

![](/images/csdirector-cstruss/resources/images/cr-roofloadmainworkspace-ibc.png)

Truss Studio calculates two factors per code to reduce the TCLL -- one for slope and one for area. The **R2** factor is applied for the slope reduction to TCLL. The **R1** factor is applied for tributary area reduction to the TCLL and the calculated area is output as **A=##**. The value for each reduction factor is output on the TDD.

![](/images/csdirector-cstruss/resources/images/cr-roofliveload-r-factor.png)

#### Designing for TCLL between 12 PSF and 20 PSF

In Truss Studio, you can use TCLL values between the minimum allowable reduction and 20 PSF. Truss Studio will not reduce the TCLL below the value entered in Standard Load. Below is an example load summary for a truss with the maximum allowable reduction applied.

![](/images/csdirector-cstruss/resources/images/cr-mactcllreduction.png)

If the allowable reduction is 14 PSF, as shown in the example, but you enter 18 PSF as the TCLL in Standard Loads, 18 PSF will be used as the actual TCLL for design purposes; the user-entered value overrides the allowable reduction.

![](/images/csdirector-cstruss/resources/images/cr-intermediatetcllexample.png)

**Additional References**

2018 International Residential Code. Copyright 2017 by International Code Council, Inc. CHAPTER 3, BUILDING PLANNING. International Residential Code for One- and Two-Family Dwellings

2018 International Building Code. Copyright 2017 by International Code Council, Inc. CHAPTER 16, STRUCTURAL DESIGN.